Abstract :
A new power system distance relay is developed in this paper. The relay is based on two operation criteria: a current criterion; and a voltage criterion. Each uses the fault component as the operating quantity, and the relay reacts only on the reactance of the transmission line. So, it is a fault component reactance relay. During external faults, the two criteria are complementary to each other, i.e. at least one of them will not be satisfied; so no maloperation will occur. During internal faults, both criteria will be satisfied even if the fault resistance is high
Keywords :
electric reactance; electrical faults; power system protection; power system relaying; power transmission lines; relay protection; current criterion; fault component reactance relay; fault resistance; internal faults; power system distance relay; transmission line; voltage criterion; Automation; Electrical resistance measurement; Feeds; Impedance; Polarization; Power system relaying; Protective relaying; Relays; Virtual manufacturing; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on