• DocumentCode
    1150877
  • Title

    Direct calculation of the stability domains of three-phase ferroresonance in isolated neutral networks with grounded neutral voltage transformers

  • Author

    Janssens, N. ; Van Craenenbroeck, Th. ; Van Dommelen, D. ; Van De Meulebroeke, F.

  • Author_Institution
    Laborelec, Linkebeek, Belgium
  • Volume
    11
  • Issue
    3
  • fYear
    1996
  • fDate
    7/1/1996 12:00:00 AM
  • Firstpage
    1546
  • Lastpage
    1553
  • Abstract
    Stability domains of ferroresonant oscillations must be computed and, if needed, countermeasures must be taken in order to avoid serious damage to the power networks´ equipment. In this paper, Clarke components are used to write the equations of a representative three-phase circuit under a canonical form and give a simple physical interpretation of the three-phase ferroresonance phenomenon. A method is proposed to approximate the quasi-periodic oscillations by periodic ones. The solutions and their domains of stability are computed by the harmonic balance method. An application to a field case is presented
  • Keywords
    ferroresonance; oscillations; potential transformers; power system stability; Clarke components; canonical form; ferroresonant oscillations; grounded neutral voltage transformers; harmonic balance method; isolated neutral networks; periodic oscillations; quasi-periodic oscillations; stability domains; three-phase circuit; three-phase ferroresonance; Capacitance; Circuit stability; Computer networks; Couplings; Damping; Equations; Ferroresonance; Inductance; Intelligent networks; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.517515
  • Filename
    517515