DocumentCode
1150877
Title
Direct calculation of the stability domains of three-phase ferroresonance in isolated neutral networks with grounded neutral voltage transformers
Author
Janssens, N. ; Van Craenenbroeck, Th. ; Van Dommelen, D. ; Van De Meulebroeke, F.
Author_Institution
Laborelec, Linkebeek, Belgium
Volume
11
Issue
3
fYear
1996
fDate
7/1/1996 12:00:00 AM
Firstpage
1546
Lastpage
1553
Abstract
Stability domains of ferroresonant oscillations must be computed and, if needed, countermeasures must be taken in order to avoid serious damage to the power networks´ equipment. In this paper, Clarke components are used to write the equations of a representative three-phase circuit under a canonical form and give a simple physical interpretation of the three-phase ferroresonance phenomenon. A method is proposed to approximate the quasi-periodic oscillations by periodic ones. The solutions and their domains of stability are computed by the harmonic balance method. An application to a field case is presented
Keywords
ferroresonance; oscillations; potential transformers; power system stability; Clarke components; canonical form; ferroresonant oscillations; grounded neutral voltage transformers; harmonic balance method; isolated neutral networks; periodic oscillations; quasi-periodic oscillations; stability domains; three-phase circuit; three-phase ferroresonance; Capacitance; Circuit stability; Computer networks; Couplings; Damping; Equations; Ferroresonance; Inductance; Intelligent networks; Voltage transformers;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.517515
Filename
517515
Link To Document