DocumentCode :
1150964
Title :
Accurate modelling of rod driven tower footing
Author :
Almeida, M.E. ; Correia de Barros, M.T.
Author_Institution :
Inst. Superior Tecnico, Tech. Univ. Lisbon, Portugal
Volume :
11
Issue :
3
fYear :
1996
fDate :
7/1/1996 12:00:00 AM
Firstpage :
1606
Lastpage :
1609
Abstract :
For evaluating the lightning performance of power transmission lines by computer simulation, accurate modelling of tower footing is very important. In particular, the decrease of the earth resistance observed for high values of the current flowing from the tower to earth has to be considered. In this paper, different modelling approaches allowing the nonlinear behaviour of the tower footing to be taken into account are overviewed, and a new model to describe the soil ionization process is presented. The proposed model corresponds to considering the ionized soil region as an equifield shell. In order to represent the ionization phenomena, the values of the resistivity on the ionized region are decreased according to the local current density, and the electric field is kept at a critical value. Deionization of the soil is also taken into account. Simulation results are presented, and compared to the published results of experimental tests
Keywords :
earthing; lightning protection; poles and towers; power overhead lines; power system analysis computing; power transmission lines; accurate modelling; computer simulation; current density; current flow; earth resistance; electric field; equifield shell; lightning performance; power transmission lines; rod driven tower footing; soil ionization process; Computer simulation; Conductivity; Current density; Earth; Grounding; Ionization; Lightning; Poles and towers; Power transmission lines; Soil;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.517523
Filename :
517523
Link To Document :
بازگشت