    Eddy-current losses in a conducting plate due to a collection of bus bars carrying currents of different magnitudes and phases

  • Author

    Del Vecchio, Robert M.

  • Author_Institution
    Waukesha Electr. Syst., Milpitas, CA, USA
  • Volume
    39
  • Issue
    1
  • fYear
    2003
  • fDate
    1/1/2003 12:00:00 AM
  • Firstpage
    549
  • Lastpage
    552
  • Abstract
    Losses in bus bars carrying AC current and passing near the tank wall in transformers can contribute significantly to stray losses and can produce high temperatures on the tank wall. Usually these losses are mitigated by moving the bus bars farther away from the wall or by placing a shield of high conductivity and low permeability on the tank wall near the bus bars. Although these losses in the wall or shield can be calculated by modern finite-element codes, an analytical method would obtain these losses quickly during the design phase. We present such a method here. The method works for an arbitrary collection of bus bars carrying currents from different phases. Applications to other situations where long cables or bus bars carrying AC currents and running parallel to a conducting plate are also possible.
  • Keywords
    busbars; conductors (electric); eddy current losses; electric current; AC current; analytical method; bus-bar losses; conducting plate; eddy-current losses; plate losses; shield losses; stray losses; transformer stray losses; transformer tank losses; Bars; Cables; Conductivity; Finite element methods; Magnetic analysis; Magnetic shielding; Permeability; Shape; Temperature; Transformers;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.2002.806353
  • Filename
    1179916