Abstract
This paper shows that the angular swings produced in a synchronous condenser by sudden application of an arc-furnace load do not in general increase the magnitude of the voltage dip produced. In addition, a criterion for stable operation of the condenser is given in terms of the system, buffer reactor, and arc-furnace transformer reactances.
Keywords
Capacitors; Circuits; Electrodes; Furnaces; Impedance; Inductors; Regulators; Steady-state; Voltage fluctuations;