DocumentCode :
1154935
Title :
Flashover on contaminated insulators with different diameters
Author :
Matsuoka, R. ; Ito, S. ; Sakanishi, K. ; Naito, K.
Volume :
26
Issue :
6
fYear :
1991
fDate :
12/1/1991 12:00:00 AM
Firstpage :
1140
Lastpage :
1146
Abstract :
The influence of the diameter on contamination flashover/withstand voltage of cylindrical insulators was investigated both for AC and DC. The increase in diameter of a cylindrical insulator significantly lowers the contaminated flashover/withstand voltage. The increase in diameter also lowers the contaminant deposit density on the insulator surface under the same contamination atmosphere. The decrease in the contamination flashover/withstand voltage is more than that implied in an existing IEC publication. The quantitative assessment of the contamination characteristics presented improves the reliability in the contamination design of cylindrical insulators having different diameters
Keywords :
flashover; insulators; contaminant deposit density; contaminated insulators; contamination characteristics; cylindrical insulators; flashover/withstand voltage; Contamination; Flashover; Helium; IEC standards; Insulation; Insulators; Linearity; Shape control; Testing; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/14.108151
Filename :
108151
Link To Document :