DocumentCode
1156437
Title
Testing the islanding protection function of photovoltaic inverters
Author
Woyte, Achim ; Belmans, Ronnie ; Nijs, Johan
Author_Institution
Dept. of Electr. Eng., Katholieke Univ. Leuven, Belgium
Volume
18
Issue
1
fYear
2003
fDate
3/1/2003 12:00:00 AM
Firstpage
157
Lastpage
162
Abstract
A major safety issue in grid-connected photovoltaics is to avoid nonintentional operation in islanding mode when the grid is being tripped. Worst-case conditions under which islanding can occur are specified analytically. The circuit that is commonly used for testing is described. The issue of appropriate test conditions with regard to reactive-power injection to the grid is discussed and the stabilizing impact of rotating machines and resonant circuits is evaluated in detail. Islanding test results for small inverters are presented. They confirm that very simple islanding protection methods that are commonly used, are likely to fail, if inverters are loaded with considerable capacitance. The obtained results support the assessment of the islanding protection function. They emphasize important points when defining new certification procedures for upcoming guidelines and standards.
Keywords
capacitance; certification; invertors; photovoltaic power systems; power system protection; reactive power; safety; 200 W; capacitance; certification procedures; grid-connected photovoltaics; islanding protection function testing; photovoltaic inverters; reactive-power injection; resonant circuits; rotating machines; safety issue; standardization; worst-case conditions; Capacitance; Certification; Circuit testing; Inverters; Photovoltaic systems; Protection; RLC circuits; Rotating machines; Safety; Solar power generation;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.2002.808410
Filename
1183727
Link To Document