DocumentCode
1156455
Title
Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters
Author
Hung, Guo-Kiang ; Chang, Chih-Chang ; Chen, Chern-Lin
Author_Institution
Dept. of Electr. Eng., Nat. Taiwan Univ., Taipei, Taiwan
Volume
18
Issue
1
fYear
2003
fDate
3/1/2003 12:00:00 AM
Firstpage
169
Lastpage
173
Abstract
The traditional frequency-shift methods for islanding detection of grid-connected PV inverters-the active frequency drift method and the slip-mode frequency-shift method-become ineffective under certain paralleled RLC loads. The automatic phase-shift method is proposed in this paper to alleviate this problem. The method is based on the phase shift of the sinusoidal inverter output current. When the utility malfunctions, the phase-shift algorithm keeps the frequency of the inverter terminal voltage deviating until the protection circuit is triggered. Simulation and experiments are performed for verification.
Keywords
invertors; photovoltaic power systems; power system protection; 1 kW; active frequency drift method; automatic phase-shift method; grid-connected photovoltaic inverters; inverter terminal voltage deviation; islanding detection; paralleled RLC loads; phase-shift algorithm; protection circuit triggering; sinusoidal inverter output current; slip-mode frequency-shift method; Frequency; Inverters; Phase detection; Photovoltaic systems; Power system harmonics; Power system protection; Power system relaying; Protective relaying; Solar power generation; Voltage;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.2002.808412
Filename
1183729
Link To Document