• DocumentCode
    1157987
  • Title

    Predicting Insulation Failures with Direct Voltage

  • Author

    Foust, C.M. ; Bhimani, B.V.

  • Volume
    76
  • Issue
    3
  • fYear
    1957
  • fDate
    4/1/1957 12:00:00 AM
  • Firstpage
    1120
  • Lastpage
    1130
  • Abstract
    A scientific study is presented of the characteristic effects of direct and alternating voltage stresses on composite insulation systems designed for alternating voltage service. It shows some of the basic differences between these two kinds of stresses, deals with a few of the limitations of the direct-voltage method of testing composite insulation designed for alternating voltage service, and describes a new mechanism of ionization, probable damage, and breakdown of such insulation under these stresses. Tests were carried out on a large number of 12 different kinds of sheet insulation samples designed either to simulate rotating machine insulation or to yield pertinent information. Equipment used in these tests was specially designed and it comprised an assembly of ten pairs of circular brass electrodes and a lightproof box containing one electrode pair and a scintillation probe for ionization detection. The latter was used as a new method for studying ionization initiation, severity, location, and spread inside the samples.
  • Keywords
    Breakdown voltage; Coils; Electrodes; Equivalent circuits; Insulation testing; Ionization; Leg; Power transformer insulation; Stress; Transformer cores;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1957.4499733
  • Filename
    4499733