• DocumentCode
    1158350
  • Title

    Dynamic Measurement of the Absolute Voltage Angle on Long Transmission Lines

  • Author

    Missout, G. ; Béland, J. ; Bédard, G. ; Lafleur, Y.

  • Author_Institution
    Institut de recherche d´´Hydro-Qudbec
  • Issue
    11
  • fYear
    1981
  • Firstpage
    4428
  • Lastpage
    4434
  • Abstract
    A new apparatus for dynamic measurement of the absolute voltage angle on long transmission lines is described. It is based on a method of synchronization by satellite and takes 30 measurements per second at three points of the Hydro-Québec network on a permanent basis. The system gives the local (or absolute) voltage phase angle (using a 60.00-Hz reference frame), the frequence at each point and the angle difference-between each pair of points. Automatic recordings of this data are made during disturbances.
  • Keywords
    Delay; Frequency synchronization; Phase measurement; Power system measurements; Power system stability; Power transmission lines; Pulse measurements; Satellites; Transmission line measurements; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316856
  • Filename