DocumentCode :
1158380
Title :
Failure of Electromagnetic Voltage Transformer Due to Sustained Over-Voltage on Switching - an Indepth Field Investigation and Analytical Study
Author :
Aggarwal, R.P. ; Saxena, N.S. ; Sharma, B.S. ; Kumar, Satish ; Krishan, Shalindra
Author_Institution :
Indian Institute of Technology
Issue :
11
fYear :
1981
Firstpage :
4448
Lastpage :
4455
Abstract :
An electromagnetic voltage transformer (EMVT) was damaged when the 220KV bus bar was being de-energised by a circuit breaker fitted with grading capacitors across its contacts. This paper describes the field investigations and analyses the phenomenon using the principle of harmonic balance. It is established that the failure occurred due to fero-resonance between CB grading capacitors and non-linear EMVT inductance causing sustained over-voltage and consequently much higher than usual current. It could be a thermal or insulation failure or both. The analytical results obtained are shown to be similar to those determined by actual field. tests.
Keywords :
Circuit breakers; Electromagnetic analysis; Electromagnetic fields; Failure analysis; Harmonic analysis; Inductance; Insulation; Switched capacitor circuits; Testing; Voltage transformers;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1981.316859
Filename :
4110529
Link To Document :
بازگشت