DocumentCode
1158472
Title
Disturbances Generated by Three-Phase Pulse-Burst-Modulated Loads and the Remedial Methods
Author
Emanuel, A.E. ; Pileggi, D.J. ; Gulachenski, E.M. ; Levitsky, F.J.
Author_Institution
Worcester Polytechnic Institute
Issue
11
fYear
1981
Firstpage
4533
Lastpage
4539
Abstract
The Pulse-Burst Modulation Method used today for three-phase load control has two major drawbacks: 1) It can generate annoyingly high levels of dc currents. 2) In four-wire systems the neutral wire carries a large single pulse of current at the beginning and end of each switching period.
Keywords
Control systems; DC generators; Furnaces; Pulse circuits; Pulse generation; Pulse modulation; Solid state circuits; Switches; Temperature control; Wire;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316832
Filename
4110540
Link To Document