DocumentCode :
1158595
Title :
Metal-Clad 4,160-Volt 350-Mva Switchgear with Symmetrical Ratings
Author :
Rietz, E.B. ; Perkins, G.O. ; Carter, W.A.
Volume :
76
Issue :
3
fYear :
1957
fDate :
4/1/1957 12:00:00 AM
Firstpage :
1397
Lastpage :
1402
Abstract :
Air break power circuit breakers of the magnetic type have been used for 2,300-and 4,160-volt service for almost the last 20 years. These breakers have been built in interrupting ratings from 50 to 250 mva (megavolt-amperes). Within the last 2 years a need has been established for breakers of higher interrupting and continuous current-carrying capacity. The need is attributable to the larger sized transformers used for distribution substations and for auxiliary power for modern generating stations. These require continuous current ratings up to 3,000 amperes and interrupting ratings up to 350 mva. The breakers and switchgear described in this paper were developed to meet this requirement. Because of industry interest in the basis of rating power circuit breakers, design tests were made to demonstrate that these breakers would meet the 350-mva interrupting rating on a symmetrical basis and with a 5-cycle interrupting time rating.
Keywords :
Associate members; Circuit breakers; Circuit testing; Electrical equipment industry; Gears; Manufacturing industries; Power generation; Substations; Switchgear; Transformers;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher :
ieee
ISSN :
0097-2460
Type :
jour
DOI :
10.1109/AIEEPAS.1957.4499804
Filename :
4499804
Link To Document :
بازگشت