DocumentCode
1159081
Title
Dynamic Stabilizer Verification Tests at the San Juan Station
Author
Ramey, D.G. ; Kimmel, D.S. ; Dorney, J.W. ; Kroening, F.H.
Author_Institution
Westinghouse Electric Corporation
Issue
12
fYear
1981
Firstpage
5011
Lastpage
5019
Abstract
The first Torsional Dynamic Stabilizers were installed at the San Juan generating station to control subsynchronous oscillations between the turbine-generator units and the series capacitor compensated transmission system. A description of these devices and their application at this plant is the subject of this paper. A field test program which included control of self-excited torsional oscillations is described. Test results verify that the Dynamic Stabilizers do control San Juan subsynchronous oscillations and allow unrestricted use of the compensation.
Keywords
Capacitors; Control systems; Distributed parameter circuits; Inductors; Power transmission lines; Protection; Switches; Temperature control; Testing; Thyristors;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316470
Filename
4110613
Link To Document