DocumentCode
1159278
Title
Harmonics and Switching Transients in the Presence of Geomagnetically-Induced Currents
Author
Mohan, N. ; Kappenman, J.G. ; Albertson, V.D.
Author_Institution
University of Minnesota
Issue
2
fYear
1981
Firstpage
585
Lastpage
593
Abstract
Electrons and protons emitted by a solar flare can be caputured by the Earth´s magnetic field. The resulting transient in the geomagnetic field can produce quasi-dc currents in electric power systems. These geomagnetically-induced currents (GICs) cause half-cycle saturation in the transformers. GICs in excess of 100 amps have been measured in the transformer neutrals. With the practice of using EHV and UHV lines for transmitting ac power over long distances and because the systems are more solidly grounded, the problems posed by GICs have become more severe. This paper presents the effect of GICs on switching operations on long EHV transmission lines. Single pole switching and secondary arc currents, long line energization, out-of-step switching etc. are considered. The effect of harmonics caused by GICs is evaluated on the harmonic filter ratings of an adjacent HVDC terminal.
Keywords
Earth; Electron emission; Geomagnetism; Magnetic field measurement; Power harmonic filters; Power system harmonics; Power system transients; Power transmission lines; Protons; Transformers;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316915
Filename
4110640
Link To Document