DocumentCode :
1159296
Title :
Development for Measurement of Operating Parameters of Synchronous Generator and Control Systems
Author :
Namba, M. ; Hosoda, J. ; Doi, S. ; Udo, M.
Author_Institution :
Kansai Electric Power Co., Inc.
Issue :
2
fYear :
1981
Firstpage :
618
Lastpage :
628
Abstract :
On load tests to measure operating parameters of apparatus in typical thermal and hydraulic power stations were performed. The results obtained by static characteristic tests of generator were greatly affected by magnetic saturation. Authors propose a new method to estimate on load synchronous reactances from no load factory tests. For dynamic characteristic test, authors conducted´a new arbitrary-axis load rejection method in addition to d-axis and q-axis load rejection method proposed by F. P. de Mello[1].
Keywords :
Character generation; Control systems; Performance evaluation; Power generation; Power measurement; Production facilities; Saturation magnetization; Synchronous generators; Testing; Thermal loading;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1981.316918
Filename :
4110643