DocumentCode
1159512
Title
Standstill Frequency Response Modeling and Evaluation by Field Tests on a 645 MVA Turbine Generator
Author
Hurley, J.D. ; Schwenk, H.R.
Author_Institution
Westinghouse Electric Corp.
Issue
2
fYear
1981
Firstpage
828
Lastpage
836
Abstract
This paper describes the testing and analysis performed under EPRI sponsorship on a 645 MVA synchronous generator to determine the suitability for dynamic simulations of a generator model derived from standstill frequency response tests. Transmission line switching tests were performed as a basis for model evaluation. Models based on standstill frequency response tests and standard design data were used in simulations of these switching events. Although the standstill frequency response model resulted in suitable simulation results, no improvement was achieved over that using the standard design data.
Keywords
Circuits; Frequency response; Performance evaluation; Power system modeling; Power system simulation; Power system transients; Rotors; Synchronous generators; Testing; Turbines;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316940
Filename
4110666
Link To Document