DocumentCode :
1159512
Title :
Standstill Frequency Response Modeling and Evaluation by Field Tests on a 645 MVA Turbine Generator
Author :
Hurley, J.D. ; Schwenk, H.R.
Author_Institution :
Westinghouse Electric Corp.
Issue :
2
fYear :
1981
Firstpage :
828
Lastpage :
836
Abstract :
This paper describes the testing and analysis performed under EPRI sponsorship on a 645 MVA synchronous generator to determine the suitability for dynamic simulations of a generator model derived from standstill frequency response tests. Transmission line switching tests were performed as a basis for model evaluation. Models based on standstill frequency response tests and standard design data were used in simulations of these switching events. Although the standstill frequency response model resulted in suitable simulation results, no improvement was achieved over that using the standard design data.
Keywords :
Circuits; Frequency response; Performance evaluation; Power system modeling; Power system simulation; Power system transients; Rotors; Synchronous generators; Testing; Turbines;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1981.316940
Filename :
4110666
Link To Document :
بازگشت