DocumentCode :
1159608
Title :
Breakdown Characteristics of Moving Transformer Oil
Author :
Ikeda, M. ; Teranishi, T. ; Honda, M. ; Yanari, T.
Author_Institution :
Toshiba Corporation
Issue :
2
fYear :
1981
Firstpage :
921
Lastpage :
928
Abstract :
As a result of investigating breakdown characteristics of moving oil, it has become clear that the breakdown voltage of ac and dc for moving oil is higher than that for stationary oil by 10-15 % at a moving velocity of 5 cm/s region; the former voltage becomes almost equal to the latter voltage in the region of 25 cm/s, and the former is reduced to lower than 90 % of the latter when the moving velocity exceeds 100 cm/s. However, for impulse voltage, the breakdown voltage of moving oil is the same as that of stationary oil.
Keywords :
Breakdown voltage; Dielectric breakdown; Dielectric measurements; Electric breakdown; Impurities; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Stress;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1981.316952
Filename :
4110678
Link To Document :
بازگشت