• DocumentCode
    1159608
  • Title

    Breakdown Characteristics of Moving Transformer Oil

  • Author

    Ikeda, M. ; Teranishi, T. ; Honda, M. ; Yanari, T.

  • Author_Institution
    Toshiba Corporation
  • Issue
    2
  • fYear
    1981
  • Firstpage
    921
  • Lastpage
    928
  • Abstract
    As a result of investigating breakdown characteristics of moving oil, it has become clear that the breakdown voltage of ac and dc for moving oil is higher than that for stationary oil by 10-15 % at a moving velocity of 5 cm/s region; the former voltage becomes almost equal to the latter voltage in the region of 25 cm/s, and the former is reduced to lower than 90 % of the latter when the moving velocity exceeds 100 cm/s. However, for impulse voltage, the breakdown voltage of moving oil is the same as that of stationary oil.
  • Keywords
    Breakdown voltage; Dielectric breakdown; Dielectric measurements; Electric breakdown; Impurities; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Stress;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316952
  • Filename
    4110678