Current Transformer Accuracy with Asymmetric and High Frequency Fault Currents
Author
Douglass, D.A.
Author_Institution
Power Technologies, Inc.
Issue
3
fYear
1981
fDate
3/1/1981 12:00:00 AM
Firstpage
1006
Lastpage
1012
Abstract
The accuracy of two commercially available window current transformers is determined for asymmetrical 60 Hz fault currents and for lower magnitude higher frequency currents. The 4000: 5, window type CT´s tested are found to be accurate to within 3 percent for frequencies up to 25 kHz for burdens of less than 10 ohms. With an antiremanence gap, such a Ct can transform a fully offset fault current of 5000 amperes and 50 millisecond time constant with less than 3 percent error for a burden resistor of 0.5 ohms
Keywords
Capacitance; Chromium; Circuit faults; Current transformers; Equivalent circuits; Fault currents; Frequency; Impedance; Testing; Transformer cores;