• DocumentCode
    1159776
  • Title

    Multi-Frequency Surge Withstand Capability Tests for Protective Relays

  • Author

    Vlah, Z.J. ; Harvey, S.M.

  • Author_Institution
    Ontario Hydro Research Division
  • Issue
    3
  • fYear
    1981
  • fDate
    3/1/1981 12:00:00 AM
  • Firstpage
    1065
  • Lastpage
    1071
  • Abstract
    The reliability of solid state protective relays in the hostile electromagnetic environment of high-voltage switchyards and substations has been improved by the use of surge withstand capability (SWC) tests. Ontario Hydro relay specifications call for a SWC test with a surge test wave having frequency, amplitude, and source impedance as variable and interdependent parameters. The need for a multi-frequency SWC test with a frequency range of 0.1 to 2 MHz is confirmed by field surveys of surge characteristics, data from actual SWC tests, and laboratory investigations of SWC frequency dependence. A simple, moderately-priced SWC tester capable of generating accurately defined test waves within the defined range of test wave parameters is described
  • Keywords
    Frequency; Power system protection; Power system relaying; Protective relaying; Relays; Solid state circuits; Substation protection; Surge protection; System testing; Wiring;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316572
  • Filename
    4110700