• DocumentCode
    1159812
  • Title

    Optimum Size and Location of Shunt Capacitors for Reduction of Losses on Distribution Feeders

  • Author

    Grainger, J.J. ; Lee, S.H.

  • Author_Institution
    Electrical Engineering Department North Carolina State University
  • Issue
    3
  • fYear
    1981
  • fDate
    3/1/1981 12:00:00 AM
  • Firstpage
    1105
  • Lastpage
    1118
  • Abstract
    New generalized procedures are developed for optimizing the net savings associated with reduction of power and energy losses through shunt capacitor placement on primary distribution feeders. These procedures are applied to realistic problems to facilitate their immediate use by the electric utility distribution system designer. It is shown that a basic principle, called here "The Equal Area Criterion", offers significant computational and physical insight into numerous problems outside the bounds of studies previously reported and widely accepted in industry
  • Keywords
    Capacitors; Computer industry; Energy loss; Physics computing; Power factor correction; Power generation economics; Power industry; Shunt (electrical); Voltage control; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316577
  • Filename
    4110705