    A Simplified Procedure for Determining the Auxiliary Bus Voltage and Angle During Bus Transfer

  • Author

    Watters, C.V.

  • Author_Institution
    Bechtel Power Corp.
  • Issue
    6
  • fYear
    1981
  • fDate
    6/1/1981 12:00:00 AM
  • Firstpage
    3066
  • Lastpage
    3076
  • Abstract
    During a power station auxiliary bus transfer the bus residual voltage and angle relative to the reserve bus voltage are critical for the first .5 second. A procedure is presented that determines the auxiliary bus voltage during the critical period of the bus transfer. For this simplified procedure a gas fired steam turbine generator auxiliary system is the test case used. The procedure is equally applicable to a nuclear steam turbine generator auxiliary system. The effect of residual motor current is reviewed. Motor speed may also be determined with reasonable accuracy.
  • Keywords
    Equations; Load flow; Medium voltage; Nuclear power generation; Power generation; Power system modeling; Steady-state; Synchronous motors; System testing; Turbines;