Title :
Arc Foot Motion, Current Distribution, Arc Short-Circuiting and Arc Clogging in an Air-Blast Interrupter
Author :
Drouet, Michel G. ; Wang, Bo-Han ; Morin, Richard
Author_Institution :
Appareillage de Reseau Institut de Recherche d´´Hydro-Quebec
fDate :
7/1/1981 12:00:00 AM
Abstract :
Tests are conducted in a commercial air-blast interrupter. The arc foot motion on the nozzle surface and the arc behavior are studied after contact separation for currents up to 25 kA rms. Arc short-circuiting between the arc column and the nozzle surface, and the distribution of the current in the arc foot during normal motion of the arc in the nozzle and during arc clogging are measured using special probes embedded in the nozzle.
Keywords :
Circuit breakers; Coils; Current distribution; Current measurement; Fluid flow; Foot; Interrupters; Performance evaluation; Probes; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1981.316676