DocumentCode :
1163168
Title :
Severe degradation of the conductor screen of service and laboratory aged medium voltage XLPE insulated cables
Author :
Hvidsten, Sverre ; Kvande, Stine ; Ryen, Arve ; Larsen, Per Bjørn
Author_Institution :
SINTEF Energy Res., Trondheim
Volume :
16
Issue :
1
fYear :
2009
fDate :
2/1/2009 12:00:00 AM
Firstpage :
155
Lastpage :
161
Abstract :
The main purpose of this paper is to show the strong correlation between corrosion of the metallic aluminum conductor and the formation of interconnected cracks / voids in the conductor screen, creating initiation sites for vented water trees in service aged medium voltage XLPE cables. The results show that porous structures in the conductor screen previously reported for laboratory aged insulation systems, also develop in the conductor screen in service aged medium voltage XLPE cables. These structures can bridge the screen and serve as path for contaminants and corrosion products from the aluminum conductor and initiate water trees. A prerequisite for the formation of such structures is the presence of liquid water at the interface between the conductor and conductor screen causing corrosion. The initiation site of such structures has been identified, and is likely caused by environmental stress cracking (ESC). Initiation sites were determined in all cables, but porous structures in the conductor screen were only observed in the cable suffered from service failure, where liquid water had entered the cable conductor between the strands. Severe degradation of the XLPE insulation was observed at the initiation sites for water trees growing from these structures.
Keywords :
XLPE insulation; ageing; conductors (electric); insulation testing; power cable insulation; power cable testing; stress corrosion cracking; trees (electrical); corrosion product; environmental stress cracking; interconnected crack; medium voltage XLPE insulated cable aging; metallic aluminum conductor screen; porous structure; water tree; Aging; Aluminum; Cable insulation; Cables; Conductors; Corrosion; Degradation; Laboratories; Medium voltage; Trees - insulation; Conductor screen, degradation, medium voltage cable, water treeing.;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2009.4784563
Filename :
4784563
Link To Document :