• DocumentCode
    1164617
  • Title

    Ligntning Insulation Coordination for a ±600 kV DC Gas Insulated Cable

  • Author

    Hileman, A.R. ; Flugum, R.W. ; Garrity, T.F.

  • Author_Institution
    Westinghouse Electric Corp.
  • Issue
    11
  • fYear
    1982
  • Firstpage
    4399
  • Lastpage
    4406
  • Abstract
    To determine the required BIL of a +600 kV dc gas-insulated cable, a probabilistic insulation coordination study was performed. An equation was developed to determine the maximum voltage on the cable as a function of directly connected highly nonlinear surge protective devices (MO). After estimating the distribution of surge voltage magnitudes and shapes which arrive at the line-cable junction, the probability of flashover within the cable was determined. The results, analyzed in terms of mean time between failures, MTBF, verified that a 1300 kV BIL was adequate.
  • Keywords
    Cable insulation; Gas insulation; Nonlinear equations; Power cable insulation; Power cables; Shape; Surge Protective Devices - c62; Surge protection; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317406
  • Filename
    4111267