Title :
Recovery Times of Vaccum Interrupters Which have Stationary Anode Spots
Author :
Frind, G. ; Carroll, J.J. ; Goody, C.P. ; Tuohy, E.J.
Author_Institution :
General Electric Research & Development Center
fDate :
4/1/1982 12:00:00 AM
Abstract :
With rectangular power current waves recovery times of a vacuum interrupter with copper-based button contacts were measured. They were found to increase from 7 , ¿at 250 A to 630 ¿s at 12 kAp, where a stationary anode spot had formed. With a stationary anode spot present recovery time was also approximately proportional to current pulse duration. An attempt was made to explain the long recovery times by evaporation from the highly heated anode after the current had ceased. In addition, some high-speed photographic observations were made on the formation of stationary anode spots.
Keywords :
Anodes; Cathodes; Cooling; Current measurement; Electric variables measurement; Electrodes; Interrupters; Motion pictures; Power measurement; Vacuum arcs;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1982.317141