• DocumentCode
    1165688
  • Title

    Recovery Times of Vaccum Interrupters Which have Stationary Anode Spots

  • Author

    Frind, G. ; Carroll, J.J. ; Goody, C.P. ; Tuohy, E.J.

  • Author_Institution
    General Electric Research & Development Center
  • Issue
    4
  • fYear
    1982
  • fDate
    4/1/1982 12:00:00 AM
  • Firstpage
    775
  • Lastpage
    782
  • Abstract
    With rectangular power current waves recovery times of a vacuum interrupter with copper-based button contacts were measured. They were found to increase from 7 , ¿at 250 A to 630 ¿s at 12 kAp, where a stationary anode spot had formed. With a stationary anode spot present recovery time was also approximately proportional to current pulse duration. An attempt was made to explain the long recovery times by evaporation from the highly heated anode after the current had ceased. In addition, some high-speed photographic observations were made on the formation of stationary anode spots.
  • Keywords
    Anodes; Cathodes; Cooling; Current measurement; Electric variables measurement; Electrodes; Interrupters; Motion pictures; Power measurement; Vacuum arcs;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317141
  • Filename
    4111394