• DocumentCode
    1165732
  • Title

    A Laboratory Study on RI, TVI and an of Insulator Strings for DC Transmission line Under Contaminated Condition

  • Author

    Fujimura, T. ; Naito, K. ; Matsuoka, R. ; Suzuki, Y.

  • Author_Institution
    NGK INSULATORS, LTD.
  • Issue
    4
  • fYear
    1982
  • fDate
    4/1/1982 12:00:00 AM
  • Firstpage
    815
  • Lastpage
    824
  • Abstract
    This paper reports the results of a laboratory study on radio interference (RI), television interference (TVI) and audible noise (AN) of contaminated insulator strings for DC transmission line. It is clarified that RIV (Radio Influence Voltage), TVI and AN levels of contaminated insulator under DC voltage condition are almost the same as those under AC voltage condition, although those of clean insulator and conductor are lower under DC voltage condition than those under AC voltage condition. So, in the DC transmission line, the noises from insulator, especially under contaminated condition, are considered more influential than those in the AC transmission line.
  • Keywords
    Conductors; Corona; Flashover; Insulation; Laboratories; Power system reliability; Power transmission lines; TV interference; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317146
  • Filename
    4111399