The "First Zero Interrupter" as an Alternative to the Fault Current Limiter
Author :
Barkan, Philip
Author_Institution :
Design Division Stanford University
Issue :
6
fYear :
1982
fDate :
6/1/1982 12:00:00 AM
Firstpage :
1607
Lastpage :
1619
Abstract :
A simplified solution to the fault current limiter problem, based upon fault current limitation after the first current loop, is formulated and examined in detail. A survey of key U.S. utilities has yielded significant quantitative information on short circuit capacity requirements, characteristic features of affected systems, and fault current statistics. Based upon consultation with manufacturers of transmission equipment and mathematical analyses, an assessment is made of the short circuit behavior of existing substation apparatus when subjected to higher-than-rated faults whose duration is limited to a single current loop.
Keywords :
Circuit breakers; Circuit faults; Current limiters; Fault current limiters; Fault currents; Interrupters; Manufacturing; Power generation economics; Statistics; Substations;