DocumentCode
1167319
Title
Composite power system health analysis using a security constrained adequacy evaluation procedure
Author
Billinton, Roy ; Lian, Guangbin
Author_Institution
Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask., Canada
Volume
9
Issue
2
fYear
1994
fDate
5/1/1994 12:00:00 AM
Firstpage
936
Lastpage
941
Abstract
This paper presents an approach to evaluating the health of a composite generation and transmission system. The functionality of the system is identified as being healthy, marginal or at risk. The outage contingencies leading the system to each of the three operating states can be identified and calculated using a security constrained adequacy evaluation procedure. The probabilities associated with the outage events in the classified domains can be utilized to calculate system operating limits and risk indices. The identified system outage events can provide power engineers with additional information which can be used to evaluate reinforcement or modifications. Studies on a hypothetical system are used to examine the effect of system load demands, facility additions and line removals on the composite system health and risk
Keywords
power system control; power system protection; power system reliability; probability; composite generation/transmission system; composite power system health analysis; facility additions; line removals; outage contingencies; power system reliability; probabilities; security constrained adequacy evaluation procedure; system load demands; system operating limits; system risk indices; Information security; Interconnected systems; Power engineering and energy; Power generation; Power system analysis computing; Power system planning; Power system reliability; Power system security; Power transmission lines; Systems engineering and theory;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.317653
Filename
317653
Link To Document