DocumentCode
1168046
Title
Forced Commutation Performance of Vaccum Switches for HVDC Breaker Application
Author
Premerlani, W.J.
Author_Institution
General Electric Research and Development Center
Issue
8
fYear
1982
Firstpage
2721
Lastpage
2727
Abstract
Tests were conducted to determine performance limits for vacuum switches under forced commutation conditions associated with a high- voltage dc (HVDC) breaker.* Circuit parameters were varied and both linear and saturable reactors were used. Single as well as two series breaks were tested. Both ac and dc recovery voltages were applied. Results confirm that the critical parameters are the current to be interrupted and the time to drive the switch current to zero. A linear reactor works nearly as well as a saturable reactor. Also, the magnitude of current injection need not be matched to the fault current; excess charge is preferred.
Keywords
Capacitance; Capacitors; Circuit breakers; Circuit testing; HVDC transmission; Inductance; Inductors; Switches; Switching circuits; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317643
Filename
4111660
Link To Document