• DocumentCode
    1168159
  • Title

    Study of Driven Ground Rods and Four Point Soil Resistivity Tests

  • Author

    Blattner, C.J.

  • Author_Institution
    Niagara Mohawk Pover Corporation
  • Issue
    8
  • fYear
    1982
  • Firstpage
    2837
  • Lastpage
    2850
  • Abstract
    A series of tests has been conducted to compare the apparent soil resistivity of a driven ground rod with the soil resistivity measurements obtained by the four point method. Both uniform and non-uniform soil conditions were encountered. A theoretical analysis is performed for the two test methods in two-layer soil conditions. An equation is derived to enable the calculation of the driven rod apparent soil resistivity based on the four point soil resistivity tests.. The actual test results are analyzed based on two-layer theoretical considerations. Possible limitations of the four point test method are discussed.
  • Keywords
    Conductivity measurement; Conductors; Contact resistance; Electrical resistance measurement; Equations; Length measurement; Performance evaluation; Soil measurements; Substations; Testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317563
  • Filename
    4111673