DocumentCode :
1168651
Title :
Thermal Relationships in an Induction Motor under Normal and Abnormal Operation
Author :
Martiny, W.T. ; McCoy, R.M. ; Margolis, H.B.
Volume :
80
Issue :
3
fYear :
1961
fDate :
4/1/1961 12:00:00 AM
Firstpage :
66
Lastpage :
76
Abstract :
Improvements in motor protection and design require knowledge of the thermal effects produced in a motor when it is operating under normal and abnormal conditions. This paper describes a series of tests that were made on a 350-hp (horsepower) 900-rpm induction motor. The tests included single-and 3-phase stall and running tests, and acceleration tests at different voltage levels and subsynchronous speeds. A comprehensive picture is obtained of steady-state and transient temperatures in the stator and the rotor. An analysis of the thermal effects in terms of possible damage to the motor is presented.
Keywords :
Circuits; Frequency; Impedance; Induction motors; Power engineering and energy; Protection; Protective relaying; Telephony; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher :
ieee
ISSN :
0097-2460
Type :
jour
DOI :
10.1109/AIEEPAS.1961.4500978
Filename :
4500978
Link To Document :
بازگشت