• DocumentCode
    1169735
  • Title

    Evaluation of the Effectiveness of Shielding and Filtering of HVDC Converter Stations

  • Author

    Daillaire, R. D. ; Maruvada, P. Sarma

  • Author_Institution
    Institut de recherche d´Hydro-Québec 1800 montée Ste-Julie, Varennes, Québec, Canada JOL 2PO
  • Volume
    9
  • Issue
    4
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    108
  • Lastpage
    109
  • Abstract
    The electromagnetic interference (EMI) generated by the periodic turn-on and turn-off of the valves is an important consideration in the design of HVDC converter stations. Remedial measures such as shielding the valve hall and filtering have been used in order to reduce the interference levels to acceptable values. The application of recently-developed Numerical Electromagnetic Code (NEC) to the problem of EMI from HVDC converter stations is investigated in this paper, with particular emphasis on evaluating the effectiveness of valve hall shielding and filtering.
  • Keywords
    Electromagnetic interference; Filtering; HVDC transmission; Insulation; Insulator testing; Laboratories; National electric code; Sea surface; Valves; Voltage; Converter Station; Electromagnetic Interference (EMI); Filtering; High Voltage Direct Current (HVDC); Valve-hall Shielding;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.1989.4310649
  • Filename