DocumentCode
1169735
Title
Evaluation of the Effectiveness of Shielding and Filtering of HVDC Converter Stations
Author
Daillaire, R. D. ; Maruvada, P. Sarma
Author_Institution
Institut de recherche d´Hydro-Québec 1800 montée Ste-Julie, Varennes, Québec, Canada JOL 2PO
Volume
9
Issue
4
fYear
1989
fDate
4/1/1989 12:00:00 AM
Firstpage
108
Lastpage
109
Abstract
The electromagnetic interference (EMI) generated by the periodic turn-on and turn-off of the valves is an important consideration in the design of HVDC converter stations. Remedial measures such as shielding the valve hall and filtering have been used in order to reduce the interference levels to acceptable values. The application of recently-developed Numerical Electromagnetic Code (NEC) to the problem of EMI from HVDC converter stations is investigated in this paper, with particular emphasis on evaluating the effectiveness of valve hall shielding and filtering.
Keywords
Electromagnetic interference; Filtering; HVDC transmission; Insulation; Insulator testing; Laboratories; National electric code; Sea surface; Valves; Voltage; Converter Station; Electromagnetic Interference (EMI); Filtering; High Voltage Direct Current (HVDC); Valve-hall Shielding;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.1989.4310649
Filename
4310649
Link To Document