DocumentCode :
117
Title :
An Inrush Current Reduction Technique for Multiple Inverter-Fed Transformers
Author :
Yu-Hsing Chen ; Ming-Yang Yeh ; Po-Tai Cheng ; Jen-Chuan Liao ; Wen-Yin Tsai
Author_Institution :
Medium Voltage Drive Bus. Dept., Delta Electron. Inc., Chungli, Taiwan
Volume :
50
Issue :
1
fYear :
2014
fDate :
Jan.-Feb. 2014
Firstpage :
474
Lastpage :
483
Abstract :
This paper introduces a transformer inrush current reduction technique for the conventional double-conversion uninterruptible power supply (UPS) feeding multiple loads and their transformers. As these loads are engaged or disengaged, their transformers are also connected or disconnected from the power lines. To avoid the inrush current, a closed-loop flux linkage control and a phase winding energizing sequence control for the incoming transformer are proposed to maintain the flux of transformers which are already engaged and of the transformer which is switched on. The proposed method can utilize the existing voltage and current sensor feedback of the UPS, and it can be seamlessly integrated with the voltage and current control. Experimental test results are provided to validate the effectiveness of the proposed method.
Keywords :
closed loop systems; electric current control; invertors; power transformers; uninterruptible power supplies; voltage control; closed loop flux linkage control; conventional double conversion uninterruptible power supply; current control; current sensor feedback; multiple inverter fed transformers; phase winding energizing sequence control; transformer inrush current reduction technique; voltage control; voltage sensor feedback; Circuit faults; Delays; Surges; Switches; Uninterruptible power systems; Voltage control; Flux compensation; inrush current; magnetic saturation; uninterruptible power supply (UPS);
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2013.2269312
Filename :
6542704
Link To Document :
بازگشت