DocumentCode :
1170003
Title :
Alternative Twelve Pulse Arrangement For Static Var Control Applications
Author :
Tam, Kwa-sur ; Lasseter, Robert H.
Author_Institution :
University of Wisconsin
Issue :
12
fYear :
1983
Firstpage :
3728
Lastpage :
3735
Abstract :
5th and 7th harmonics generated by a static var control system may be eliminated by the conventional twelve pulse arrangement employing wye-wye and wye-delta transformers or by an alternative scheme described in this paper. The alternative scheme offers the advantages that only one transformer is needed and generally less transformer loss is generated. Theoretical analysis and digital simulation of the new scheme are presented. The performances of the alternative scheme under balanced and unbalanced conditions have been investigated.
Keywords :
Power harmonic filters; Power system harmonics; Power system modeling; Power system simulation; Power system transients; Pulse power systems; Reactive power; Static VAr compensators; Thyristors; Transformers;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1983.317865
Filename :
4111895
Link To Document :