DocumentCode
1170297
Title
High-voltage line-dropping switching stresses
Author
Stokes, A.D.
Author_Institution
Sch. of Electr. Eng., Sydney Univ., NSW, Australia
Volume
139
Issue
1
fYear
1992
fDate
1/1/1992 12:00:00 AM
Firstpage
21
Lastpage
26
Abstract
Results are given of SF6 circuit-breaker restrike waveforms during no-load, live-line switching operations on a 362 kV network, together with laboratory tests of the early dielectric recovery of the circuit breaker. It is shown that the tendency to restrike is assisted by the excellent interrupting ability of the breaker when the initial transient recovery voltage rises at the very slow rate typical of `stiff´ networks
Keywords
circuit breakers; restriking voltage; sulphur compounds; transients; 362 kV; SF6 circuit breakers; dielectric recovery; high voltage; line-dropping switching stresses; live-line switching; no-load switching; restrike waveforms; transient recovery voltage rises;
fLanguage
English