Title :
Proposed New Breaker Ratings and Their Efect on Application for Industrial Systems
fDate :
4/1/1961 12:00:00 AM
Abstract :
Simplified breaker application to industrial systems is proposed. Multiplier curves and tables provide the answer. These curves were developed (1) by superimposing calculated induction motor fault currents on synchronous-machine-source fault currents, and (2) by adding "k" factor curves which are an indication of the momentary limits of the breaker. Built-in asymmetrical capability allows breakers to be applied to industrial systems independently of breaker rated interrupting time. One symmetrical-current (E/X) calculation is adequate for breaker application.
Keywords :
Circuit breakers; Circuit faults; Fault currents; Impedance; Information analysis; Protection; Protective relaying; Standby generators; Transmission lines; Voltage;
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
DOI :