DocumentCode :
1170935
Title :
Performance of 115 kV Fiberglass Transmission Crossarms in Wet and Salt Fog Environments
Author :
Shah, K.R. ; Sarkinen, C.F. ; Verma, V.
Author_Institution :
Shah & Associates, Inc.
Issue :
4
fYear :
1983
fDate :
4/1/1983 12:00:00 AM
Firstpage :
805
Lastpage :
811
Abstract :
This paper discusses 60 Hz-dielectric tests performed on 115 kV solid fiberglass transmission crossarm-insulator asserblies to evaluate their performance in wet and salt fog envirorents. Testing included the following variables: (1) wet and dry conditions, (2) new and used crossarms and insulators, (3) type and number of insulators, and (4) salt fog salinity. Analysis of test results shows that the surface coating of fiberglass insulation is susceptible to degradation in a salt fog enviroment. Once this coating is eroded and the glass fibers are exposed, carbonized tracking develops. The fiberglass crossarm thus loses its electrical strength.
Keywords :
Flashover; Insulation life; Insulator testing; Laboratories; Optical fiber testing; Pollution measurement; Porcelain; Surface fitting; Urban pollution; Voltage measurement;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1983.317943