• DocumentCode
    1170982
  • Title

    Experiences in the Internal Inspection and Maintenance Works on Gas Insulated Equipment in the Field

  • Author

    Kuwahara, Hiroshi ; Tanabe, Toshio ; Sasamoto, Sakae ; Ogawa, Atsumichi ; Nitta, Tohei

  • Author_Institution
    Mitsubishi Electric Corporation
  • Issue
    4
  • fYear
    1983
  • fDate
    4/1/1983 12:00:00 AM
  • Firstpage
    843
  • Lastpage
    851
  • Abstract
    Data have been collected through the internal inspections and maintenance works on the gas insulated equipment working in the field. Wearing of contact of circuit breakers by repetitive interruptions of current is the determining factor for internal maintenance. Factors like the quality of sealings, conditions of absorbent, deteriorative influence of arc decomposition products etc. are not the factors that require internal inspections. Practical problems in the works inside the enclosure while the neighboring part of the substation is in operation are discussed basing on the experiences in the field.
  • Keywords
    Circuit breakers; Dielectrics and electrical insulation; Gas insulation; Geographic Information Systems; Inspection; Power & Energy Society; Samarium; Substations; Switchgear; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.317948
  • Filename
    4112008