Title :
New Method for Locating Transmission Line Ground Faults
Author :
Lantz, Martin J.
fDate :
4/1/1962 12:00:00 AM
Abstract :
The current ratio method has yielded good results for ground fault location, however, it is dependent on current readings from both ends of a 2-terminal transmission line. The proposed method is operable from current data, namely, the phase and residual currents, from a single terminal. A distinctive ratio curve is obtained for circuits containing series capacitors, and the method provides a means for locating ground faults on 3-terminal circuits.
Keywords :
Cable insulation; Capacitors; Circuit faults; Current measurement; Dielectric breakdown; Dielectrics and electrical insulation; Distributed parameter circuits; Fault location; Insulation testing; Transmission lines;
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
DOI :