DocumentCode :
1171403
Title :
New Method for Locating Transmission Line Ground Faults
Author :
Lantz, Martin J.
Volume :
81
Issue :
3
fYear :
1962
fDate :
4/1/1962 12:00:00 AM
Firstpage :
134
Lastpage :
136
Abstract :
The current ratio method has yielded good results for ground fault location, however, it is dependent on current readings from both ends of a 2-terminal transmission line. The proposed method is operable from current data, namely, the phase and residual currents, from a single terminal. A distinctive ratio curve is obtained for circuits containing series capacitors, and the method provides a means for locating ground faults on 3-terminal circuits.
Keywords :
Cable insulation; Capacitors; Circuit faults; Current measurement; Dielectric breakdown; Dielectrics and electrical insulation; Distributed parameter circuits; Fault location; Insulation testing; Transmission lines;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher :
ieee
ISSN :
0097-2460
Type :
jour
DOI :
10.1109/AIEEPAS.1962.4501284
Filename :
4501284
Link To Document :
بازگشت