• DocumentCode
    1171452
  • Title

    Dynamic Behavior of a 220-Kv Dead-End Suspension Bus during Short Circuit

  • Author

    Atwood, A.T., Jr. ; Mills, M.H. ; Downs, D.I. ; Stone, H.M.

  • Volume
    81
  • Issue
    3
  • fYear
    1962
  • fDate
    4/1/1962 12:00:00 AM
  • Firstpage
    153
  • Lastpage
    167
  • Abstract
    A full-size 220-kv dead-end twin-bundled conductor suspension bus was subjected to short-circuit currents of various magnitudes and durations. Transducers and instruments available allowed the measurement and recording of many physical variables during these tests. Maximum short-circuit magnitude was 30,000 rms amperes. Short-circuit currents cause dynamic forces to be applied to the bus conductors, hardware, and towers. The major shock force is a result of the twin conductors being pulled together between spreaders by the short-circuit magnetic forces. The number and location of twin conductor spreaders have considerable influence on the peak magnitude of the dynamic forces. Electrical and mechanical damage to conductors as a result of a short circuit was negligible. This suspension bus design proved to be adequate for a shortcircuit duty of 10 million kva (kilovoltamperes) at 220 kv, and with minor modifications it may be adequate for 20 million kva at 220 kv.
  • Keywords
    Circuit testing; Conductors; Electric shock; Hardware; Instruments; Magnetic forces; Magnetic levitation; Magnetic recording; Poles and towers; Transducers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1962.4501289
  • Filename
    4501289