• DocumentCode
    1171604
  • Title

    The Constant and Overload Behavior or Oil-Filled Transrormers

  • Author

    Reber, H.

  • Volume
    81
  • Issue
    3
  • fYear
    1962
  • fDate
    4/1/1962 12:00:00 AM
  • Firstpage
    235
  • Lastpage
    241
  • Abstract
    Two methods are described that enable calculation of transient parameters for simple exponential relationships, whenever certain test data are available. These two methods were specifically derived for transformer cooling and may be applied whenever top oil temperature rise measurements over a reasonable part of a heat run are available. After the transient parameters have been determined, overload temperatures may be calculated and loss of life estimated.
  • Keywords
    Circuit faults; Delay; Equations; Fault currents; Petroleum; Protection; Protective relaying; Temperature measurement; Transformers; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1962.4501307
  • Filename
    4501307