• DocumentCode
    1171727
  • Title

    Derating Cables in Trays Traversing Firestops or Wrapped in Fireproofing

  • Author

    Esteves, Oscar M.

  • Author_Institution
    Bechtel Power Corporation
  • Issue
    6
  • fYear
    1983
  • fDate
    6/1/1983 12:00:00 AM
  • Firstpage
    1478
  • Lastpage
    1481
  • Abstract
    Using ICEA Standard P-54-440 as the basis, this paper derives simple equations to calculate the maximum permissible load losses for cables in trays passing through firestops or covered with fireproofing material. From these loss values are deduced ampacity multiplying factors which when applied to the ICEA standard ampacities, provide the permissible ampere loading for the cables. A basic factor in the derivation is the use of previously published experimental data relating to the heating of cables in firestops to calculate the thermal conductance of the firestops.
  • Keywords
    Cables; Conductors; Equations; Fires; Immune system; Power generation; Temperature; Thermal conductivity; Thermal factors; Thermal resistance;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.317856
  • Filename