Title :
Dynamic Thermal Line Ratings Part II Conductor Temperature Sensor and Laboratory Field test Evaluation
Author :
Foss, Stephen D. ; Lin, Sheng H. ; Stillwell, Howard R. ; Fernandes, Roosevelt A.
Author_Institution :
General Electric Company
fDate :
6/1/1983 12:00:00 AM
Abstract :
An outdoor laboratory test facility was utilized to evaluate the performance of the dynamic ampacity rating algorithm, developed in Part I, and a prototype conductor sensor module for measuring conductor surface temperature, conductor current and ambient air temperature. The test facility consisted of a fully instrumented outdoor mock conductor test loop and a real time data acquisition system. Both steady state and transient load tests were performed and analyzed under a wide variety of meteorological conditions. The ampacity predictions observed were consistent with laboratory test measurements. Cor- relations obtained between sensor module measurements and calibrated sensors was excellent over the intend- ed range of application of the sensor module.
Keywords :
Conductors; Current measurement; Heuristic algorithms; Laboratories; Prototypes; Temperature measurement; Temperature sensors; Test facilities; Testing; Thermal conductivity;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1983.317796