Title :
Developmenbt of Power Vacuum Interrupters
Author :
Lee, T.H. ; Greenwood, Allan ; Crouch, D.W. ; Titus, C.H.
fDate :
4/1/1962 12:00:00 AM
Abstract :
The practicality of using vacuum interrupters for switchgear applications has been demonstrated by the successful development of a number of prototype devices. Interrupting tests have been made at currents up to 43,000 amp (amperes) at 15.5 kv and recovery rates up to 6,000 volts/¿sec (per microsecoind). This has been achieved by resolvinlg many difficult technical problems, so that the vacuum interrupter now closelyr approaches the functional specification of an ideal interrupting device.
Keywords :
Electric machines; Energy conversion; Interrupters; Lagrangian functions; Nonlinear equations; Power systems; Tensile stress; Torque; Transforms; Voltage;
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
DOI :