• DocumentCode
    1172683
  • Title

    A 2-Cycle 138-Kv 10,000,000-Kva Air-Blast Circuit Breaker Design Considerations and Field Tests at Philip Sporn Station

  • Author

    Naef, Otto ; Beehler, J.E. ; Shores, R.B. ; Beatty, J.W.

  • Volume
    81
  • Issue
    3
  • fYear
    1962
  • fDate
    4/1/1962 12:00:00 AM
  • Firstpage
    801
  • Lastpage
    812
  • Abstract
    A 2-cycle 138-kv 10,000-mva (megavolt-ampere) air-blast circuit breaker has been developed and field tested. Insofar as is known, this is the first 2-cycle breaker for transmission line voltages. The breaker interrupted both transmission line and bus faults while mounted on the trailer on which it was shipped. The maximum breaker duty was 10,230 mva. It is believed this is the highest fault duty ever imposed on a 138-kv breaker in a field test. The longest interrupting time was 1.85 cycles. The breaker rating is based on the proposed, symmetrical rating structure.
  • Keywords
    Assembly; Circuit breakers; Circuit faults; Circuit testing; Debugging; Distributed parameter circuits; Engineering drawings; Logic; Power transmission lines; Switchgear;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1962.4501426
  • Filename
    4501426