DocumentCode :
1172856
Title :
Electrical Features of the Glen Canyon Power Plant and Switchyard
Author :
Rose, C.L. ; Lloyd, L.W.
Volume :
81
Issue :
3
fYear :
1962
fDate :
4/1/1962 12:00:00 AM
Firstpage :
901
Lastpage :
906
Abstract :
The Glen Canyon power plant has eight 125,000-kva 0.90-power-factor 13.8-kv generators. Power is transformed from generator voltage by three banks of 345-13.7-kv single-phase FOW (oil-immersed forced-oil-cooled with forced-water cooler) transformers and one bank of 230-13.8-kv single-phase FOW transformers. Switching facilities consisting of a 345-kv ring bus using six circuit breakers and a 7-breaker 230-kv installation are provided to connect the power plant circuits to the transmission system.
Keywords :
Bridge circuits; Circuit breakers; Power generation; Power transmission lines; Reservoirs; Rivers; Surges; Switching circuits; Transformers; Turbines;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher :
ieee
ISSN :
0097-2460
Type :
jour
DOI :
10.1109/AIEEPAS.1962.4501448