DocumentCode
1173007
Title
Results from the First Year Operation of Project EHV
Author
Abetti, P.A. ; Laforest, J.J. ; Lindh, C B. ; Maccarthy, D.D.
Volume
81
Issue
3
fYear
1962
fDate
4/1/1962 12:00:00 AM
Firstpage
968
Lastpage
976
Abstract
Project EHV was operated successfully and almost continuously at the 500-kv level for the first year of tests starting in December 1960; operation is continuing. A maximum voltage of 770 kv was attained. Corona loss and radio influence (RI) performance were very satisfactory. Corona loss at the 500-kv operating level was negligible during fair weather. Correlation has been established between values of corona loss, RI, and audible sound measured simultaneously.
Keywords
Conductors; Corona; Insulation; Performance loss; Poles and towers; Power transformers; Read only memory; Substations; Testing; Voltage;