DocumentCode :
1173281
Title :
Cement Growth Failure of Porcelain Suspension Insulators
Author :
Cherney, E.A.
Author_Institution :
Ontario Hydro
Issue :
8
fYear :
1983
Firstpage :
2765
Lastpage :
2774
Abstract :
The paper provides the results and analyses oFinvestigations into porcelain suspension insulator failures on the Ontario Hydro system. The high failure rate of suspension insulators on transmission and distribution lines has been attributed to the volume expansion of the neat cement, a process commonly referred to as "cement growth". Analytical analysis of the suspension insulator design and autoclave expansion tests on insulators support the cement growth failure mechanism.
Keywords :
Assembly; Dielectrics and electrical insulation; Failure analysis; History; Insulator testing; Manufacturing; North America; Porcelain; Power transmission lines; Safety;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1983.317959