Title :
Single Phase Switching Tests on the AEP 765 KV System-Extinction Time for Large Secondary Arc Currents
Author :
Fakheri, A.J. ; Shuter, T.C. ; Schneider, J.M. ; Shih, C.H.
Author_Institution :
American Electric Power Service Corporation
Abstract :
Single Phase Switching (SPS) tests were performed on AEP´s Kammer-Marysville 765 kV line during April of 1980 in order to determine the self-extinction times of large secondary arc currents in circuits with varying degrees of SPS compensation. Five fault tests were performed and the results are presented along with an analysis of various secondary arc parameters such as: volt-ampere characteristic, air gap dielectric recovery, harmonic spectrum and energy. An arc model was developed and verified in a computer simulation of one of the test circuits.
Keywords :
Automatic testing; Circuit faults; Circuit testing; Computer simulation; Dielectrics; Harmonic analysis; Performance analysis; Performance evaluation; Switching circuits; System testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :